The 63-1024 can be used in all areas where P******oelectric Smoke Detectors are required. The wide range smoke chamber makes the 63-1024 well suited for fires ranging from smoldering to flaming fires.
Light Source GaAlAs Infrared Emitting Diode
Rated Voltage 17.7 - 30.0 VDC
Working Voltage 15.0 - 33.0 VDC
Maximum Voltage 42 VDC
Supervisory Current 45mA @ 24 VDC
Surge Current 160mA max. @ 24 VDC
Alarm Current 150mA max. @ 24 VDC
Air Velocity Range 0-4000 fpm
Ambient Temperature 32°F to 120°F (0°C to 49°C)
Color & Case Material Bone PC/ABS Blend
Sensitivity Test Feature Automatic Sensitivity window verification test