Mô tả sản phẩm: Thiết bị đo cài đặt điện đa chức năng Sonel MPI-505
Measurement range acc. to IEC 61557: 0.13...1999Ω for a 1.2 m test lead:
Display range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(5% m.v +5 digits) |
20,0...199,9Ω | 0,1Ω | |
200...1999Ω | 1Ω |
• Nominal operating voltage UnL-N/ UnL-L: 115/200V, 220/380V, 230/400V, 240/415V
• Operating voltage range: 100…264V (for ZL-PE i ZL-N) and 100…440V (for ZL-L)
• Nominal power network frequency fn: 50Hz, 60Hz
• Operating frequency range: 45…65Hz
• Maximal measurement current: 23A at 230V (10ms), 40A at 400V (10ms),
• Verification of correctness of the PE terminal connection with a touch (for ZL-PE)
Measurement of short-circuit loop impedance ZL-PE in the RCD mode
Measurement range acc. to IEC 61557: 0.5...1999Ω for a 1.2 m test lead
Display range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(6% m.v + 10 digits) |
20,0...199,9Ω | 0,1Ω | ±(6% m.v + 5 digits) |
200...1999Ω | 1Ω |
• Does not trip RCD breakers of RCD current IΔn ≥ 30mA
• Nominal operating voltage Un: 115V, 220V, 230V, 240V
• Operating voltage range: 100…264V
• Nominal power network frequency fn: 50Hz, 60Hz
• Operating frequency range: 45…65Hz
• Verification of correctness of the PE terminal connection with a touch probe
Measurement of insulation resistance
Measurement range acc. to IEC 61557-2:
• for UN = 100V: 100kΩ...500MΩ
• for UN = 250V: 250kΩ...1GΩ
• for UN = 500V: 500kΩ...2GΩ
• for UN = 1000V: 1MΩ...3GΩ
Display range*) |
Resolution | Accuracy |
0...1999kΩ | 1kΩ | ±(3% m.v. + 8 digits) |
2,00...19,99MΩ | 0,01MΩ | |
20,0...199,9MΩ | 0,1MΩ | |
200...500MΩ | 1MΩ | |
200...1000MΩ | 1MΩ | |
200...1999MΩ | 1MΩ | |
2,00...3,00GΩ | 0,01GΩ | ±(4% m.v. + 6 digits) |
*) not exceeding the measurement range for a given voltage.
• Measurement voltage: 100 V, 250 V, 500 V and 1000 V
• Detection of presence of voltage before the measurement
• Discharge of the measured object after the measurement
• Measurements of voltage on terminals +RISO, -RISO within the range of: 0…440 V
• Measurement current < 2 mA
Low-voltage measurement of circuit continuity and resistance
Measurement of protective conductor continuity with current ±200 mA
Measurement range acc. to IEC 61557-4: 0.12...400Ω
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(2% m.v. + 3 digits) |
20,0...199,9Ω | 0,1Ω | |
200...400Ω | 1Ω |
• Voltage on open terminals: 4…9V
• Output current at R<2Ω: min. 200mA
• Compensation of test lead resistance
• Measurements for both polarities of current
Measurements of RCD breaker parameters (operating voltage range 100…264 V):
RCD tripping test and measurement of tA trip time (for the tA measurement function)
RCD type | Test current multiplier |
Range | Resolution | Accuracy |
Standard | 0,5*IΔn | 0...300ms | 1 ms |
± (2% m.v. + 2 digits) |
1*IΔn | ||||
2*IΔn | 0...150ms | |||
5*IΔn | 0...40ms | |||
Selective | 0,5*IΔn | 0...500ms | ||
1*IΔn | ||||
2*IΔn | 0...200ms | |||
5*IΔn | 0...150ms |
*for IΔn= 10mA and 0.5 IΔn uncertainty is + 2% m.v. + 3 digits
Measurement of IA RCD trip current for sinusoidal differential current:
Selected current |
Measurement range |
Resolution | Test current |
Accuracy |
10mA | 3,3...10,0mA | 0,1mA | 0,3xIΔn...1,0xIΔn | ± 5% IΔn |
30mA | 9,0...30,0mA | |||
100mA | 33...100mA | 1mA | ||
300mA | 90...300mA | |||
500mA | 150...500mA | |||
1000mA | 330...1000mA |
• Capability of starting the measurement from either positive or negative half-period of forced leakage current
Measurement of IA RCD trip current for pulsating unidirectional current:
Selected |
Measurement range |
Resolution |
Test |
Accuracy |
10mA | 4...20,0mA | 0,1mA | 0,4 x IΔn ...2,0 x IΔn | ±10% IΔn |
30mA | 12,0...42,0mA | 0,4xIΔ..1,4xIΔn | ||
100mA | 40,0...140mA | 1mA | ||
300mA | 120...420mA | |||
500mA | 200...700mA |
• Capability of measurement for either positive or negative half-periods of forced leakage current
• Maximal time of the measurement current flow is 3200 ms