Mô tả sản phẩm: Công tắc giám sát đóng mở van cổng (UL/FM) Potter OSYSU-1
UL, ULC, and CSFM Listed, FM Approved, NYMEA Accepted, CE Marked
Dimensions: 6.19"L X 2.25"W X 5.88"H
15,7cm L X 5,7cm W X 14,6cm H Weight: 2 lbs. (0,9 kg.)
Enclosure: Cover - Finish -
Base -
Die-Cast
Red Spatter Enamel Die Cast Zinc
All parts have corrosion resistant finishes. Cover Tamper: Tamper resistant screws,
Optional cover tamper kit available.
Contact Ratings:
OSYSU-1: One set of SPDT (Form C) OSYSU-2: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC
2.50 Amps at 30VDC resistive
Environmental Limitations:
NEMA 4 and NEMA 6P Enclosure (IP67) when used with
appropriate watertight conduit fittings.
Indoor or Outdoor use (Not for use in hazardous locations. See bulletin no. 5400705 OSYS-U-EX for hazardous locations.)
Temperature Range: 40°F to 140°F (40°C to 60°C)
General Information
The OSYSU is used to monitor the open position of an OS&Y (outside screw and yoke) type gate valve. This device is available in two models; the OSYSU-1, containing one set of SPDT (Form C) contacts and the OSYSU-2, containing two sets of SPDT (Form C) contacts. These switches mount conveniently to most OS&Y valves ranging in size from 2" to 12" (50mm to 300mm). They will mount on some valves as small as 1⁄2" (12,5mm).
The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replacement or additional cover screws and hex keys are available. See Ordering Information.
Optional Cover Tamper Switch
Afieldinstallablecovertamperswitchisavailableasanoptionwhichmay be used to indicate removal of the cover. See Ordering Information.
Testing
The OSYSU and its associated protective monitoring system should be inspected and tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
Conduit Entrances:
2 knockouts for 1/2" conduit provided
Service Use:
Automatic Sprinkler
One or two family dwelling
Residential occupancy up to four stories National Fire Alarm Code
Ordering Information Model Description
OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch)
OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch)
Cover Screw
Hex Key for Cover Screws and Installation
Adjustments
-- Optional Cover Tamper Switch Kit
NFPA-13 NFPA-13D NFPA-13R NFPA-72
Stock No.
1010106
1010206
5490424
5250062