Mô tả sản phẩm: Bộ lưu điện UPS Tescom Neoline 220 20kVA XL
• Output power factor up to 0.8 – applicable to the tendency of future load evolution, and deliver higher payload capacity;
• Total power factor up to 90% can minimize the power loss of UPS and utilization cost for user;
• Active power factor correction (PFC) technology allows the input power factor approaching to 1, dramatically reducing the immunity on utility grid;
• Wider range of input voltage tailored for China grid can be suitable to all severe environments;
• Excellent input frequency range makes UPS suitable to different power supply devices, i.e. generator set;
High Reliability
• Its cut-edge digital control technology of DSP (Digital Signal Processor) can deliver higher quality ,performance and reliability
• Higher payload and overload capability, better load compatibility, and suitable for various load type
• Powerfull Interference immunity capability in compliance with EMC requirements of IEC61000 -4, deliver your device a clean electric environment.
Key Features
• Its cut-edge digital technology of DSP (Digital Signal Processor), can greatly improve the products performance and system reliability, and deliver a compact integration with higher power density;
• Output power factor up to 0.8 – applicable to the tendency of future load evolution, and deliver higher payload capacity;
• Higher payload and overload capability, better load compatibility, and suitable for various load type;
• Total power factor up tp 90% can minimize the power loss of UPS and utilization cost for user;
• High Scalability: fully meet the customer’s demands;
• Emergency Power Off (EPO): UPS can be instantly shut off in case of any emergency;
• Powerful interference immunity capability in compliance with EMC requirements of IEC61000 -4, deliver your device a clean electric environment.
MODEL
|
NEOLINE 210
|
NEOLINE 215
|
NEOLINE 220
|
||||
10kVA
|
10kVA XL
|
15kVA XL
|
20kVA XL
|
||||
Capacity
|
10kVA/8kW
|
15kVA/12kW
|
20kVA/16kW
|
||||
Norminal voltage
|
380/400/415 VAC 3P + N + G
|
||||||
Norminal frequency
|
50Hz. / 60Hz.
|
||||||
INPUT
|
|||||||
Voltage range
|
115 VAC ~ 300 VAC
|
120 VAC ~ 275 VAC
|
|||||
Frequency range
|
50Hz:(46~54Hz);60Hz:(56Hz~64Hz)
|
||||||
Power factor (at full load)
|
> 0.95
|
||||||
OUTPUT
|
|||||||
Voltage precision
|
220/230/240 x (1 ± 2%) VAC
|
||||||
Frequency precision
|
50Hz. / 60Hz.. ± 0.05Hz.
|
||||||
Power factor
|
0.8
|
||||||
Harmonic distortion
|
Linear load < 3% Non-linear < 6%
|
||||||
Overload capacity
|
105%-125%,60s switch to by pass, 125%-150%,30s switch to by pass, 60s cut off output; > 150%, 0.5s switch to by pass
|
||||||
Current crest ratio
|
3:1
|
||||||
Transfer time
|
0 ms (AC mode ↔ DC mode);(AC mode ↔ Bypass < 4ms)
|
||||||
BATTERY
|
|||||||
DC Voltage
|
192 VDC
|
||||||
Recharge time
|
5 hours to 90% (it means standard model which battery inside UPS)
|
||||||
Charging current
|
2A
|
4A
|
|||||
PANEL DISPLAY
|
|||||||
LCD
|
UPS status, input/output voltage and frequency, battery voltage, capacity, load temperature, history records, adjust Voltage ECO mode
|
||||||
COMMUNICATION
|
|||||||
Communication port
|
RS232, SNMP Card (optional), USB port (optional)
|
||||||
WORKING ENVIRONMENT
|
|||||||
Temperature
|
0°C – 40°C
|
||||||
Relative humidity
|
< 95% (non-condensing)
|
||||||
Storage temperature
|
0°C – 40°C
|
||||||
Altitude
|
< 1000m.
|
||||||
Acoustic noise
|
< 55 dBA
|
||||||
PHYSICAL CHARACTERISTICS
|
|||||||
Weight (kg)
|
N.W (kg)
|
68
|
47
|
51.2
|
|||
G.W (kg)
|
73
|
53
|
58.5
|
||||
Dimensions (mm) HxWxD
|
896x248x500
|
642x248x500
|