Construction
The GEMU 1434 µPos is a digital electro-pneumatic positioner for process valve control.
Designed for simple, safe and quick use with valves with strokes < 25mm.
The positioner, travel sensor, switching valves and status LEDs are integrated in a solid compact housing with transparent cover. Pneumatic and electrical connections are in one mounting direction to save space and enable easy access.

Features

  • Simple use and operation
  • Direct or separate positioner mounting to the process valve
  • For single acting normally open or normally closed linear actuators
  • Multi-point calibration for optimum valve adaption
  • Optimized initialization and valve control
  • Fail safe design with "air exhaust" or "stayput" versions

Advantages

  • No air consumption when idle
  • Simple mounting to various valve actuators
  • Simple commissioning due to automatic initialization
  • speed-AP function, for quick mounting and initialization
  • Simple operation, no settings necessary



GEMU1434 µPos Intelligent Positioner




Dimensional Drawings


 









Specifications · Directives · Operating Conditions · Materials · Parts Required for Direct Mounting · Parts Required for External Mounting





Specifications




Type

1434

Field Bus

Without (3-wire version)

Accessory

Accessory

Action

Single acting, "air exhaust"
Single acting, "stayput"

Set Value (Analogue Input)

0-10 V set value input
0-20 mA set value input
4-20 mA set value input

Material

Aluminium base, PP cover
Stainless steel base, PP cover

Pneumatic Connection

Air supply / outgoing air via M5 connection thread
Air supply / outgoing air via push-in connector angle, 4 mm
Air supply / outgoing air via push-in connector angle, 6 mm

Option

0-10 V actual value output
0-20 mA actual value output
4-20 mA actual value output
Without

Flow Rate

15 lpm

Travel Sensor

Potentiometer external, M12 connector
Potentiometer, 10 mm length
Potentiometer, 30 mm length

Protection Class to EN 60529

IP 65

Weight

220 g

Mounting Position

Optional

Speical Feature

Fail safe function in case of compressed air or power supply failure.
Dependent on the positioner version the air supply line of the process valve is vented ("air exhaust" version) or closed ("stayput version") in case of power or air supply failure.





Directives




Immunity to Interference

EN 61000-6-2

Emission of Interference

EN 61000-6-4 (class B)





Operating Conditions




Ambient Temperature

0 to +60 ºC

Storage Temperature

-10 to +60 ºC

Air Supply

1 to 10 bar at 40°C
1 to 8 bar at 60°C

Control Medium

Air or inert gases to ISO 8573-1, class 3,3,3

Air Consumption (when Idle)

0 lpm

Air Output

15 lpm





Materials




Housing Cover

Polypropylene (UV-stabilized)

Housing Base

Anodized aluminium or stainless steel


 

                                        GEMU 1436 cPos Intelligent Positioner




Construction
The GEMU 1436 cPos is a digital electropneumatic positioner with an optional integrated process controller for the control of liquids, gases and steam in conjunction with pneumatically operated process valves. The positioner exactly adjusts the stroke of the process valve. When using the optional process controller the signals from a process sensor (e.g. flow, level, pressure, temperature) are detected and the media adjusted according to the specified set value. A membrane keypad and backlit display are on the front of the housing whilst pneumatic and electrical connections are on the rear. Integrated pneumatic throttles enable the control air to be regulated in a way that the positioner can be set to suit different valve actuators and operating times.

Features

  • For use with single and double acting linear and quarter turn actuators
  • Multi point calibration for optimum valve adaptation
  • Process and position controller are synchronized with each other
  • Parameterisation during operation
  • Optimized initialisation and valve control (speedAP function)
  • Choice of direct mounting to process valve or remote mounting


Advantages

  • Digital inputs (option) for variable function control for automation
  • Field bus interfaces e.g. Profibus DP, DeviceNet (option)
  • No air consumption when idle
  • Simple mounting to various valve actuators
  • Access rights via different user levels
  • Integrated webserver
  • Simple commissioning and versatile operating facilities-fascia buttons-PC connection with Internet browser MS® Internet explorer
  • e.sycom interface for connecting a bluetooth module or industrial
  • modem to enable access via PDA or PC



GEMU 1436 cPos Intelligent Positioner




Dimensional Drawings











Specifications · Directives · Electrical Data · Travel Sensor · Controller Information · Operating Conditions · Main Functions · Materials





Specifications




Field Bus

DeviceNet
Profibus-DP
Without Field Bus

Action

Double Acting
Single Acting

Device Version

Position + Process Controller
Position Controller

Options

2 additional digital inputs 24 V DC
Without Options

Flow Rate

100 lpm
180 lpm

Travel Length1

For external potentiometer, M12 connector, 5-pin
Potentiometer, 30 mm length
Potentiometer, 50 mm length
Potentiometer, 75 mm length
Rotary potentiometer, 90°

Protection Class to EN 60529

IP 65

Weight

600 g

Mounting Position

Optional

Speical Feature

Safety function during air or power supply failure


1 The required travel length depends on the max. stroke of the process valve and must be selected accordingly.





Directives




EC Low Voltage Directive

73/23/EEC

EMC Directive

89/336/EEC

Emission of Interference

EN 50081-1

Immunity to Interference

EN 61000-6-2





Electrical Data




Power Supply

Uv = 24 V DC ± 10%

Power Consumption

ltyp = 100 mA (at 24 V DC) (for 100 lpm flow rate)
ltyp = 140 mA (at 24 V DC) (for 180 lpm flow rate)

Set Value (Analogue Input)

0/4 - 20 mA (selectable)

Actual Value, External (Analogue Input)

0/4 - 20 mA (selectable) (For Position + Process Controller device version)

External Travel Sensor (Analogue Input)

RG 1 - 10kΩ (For external potentiometer, M12 connector, 5-pin)

Function (Digital Input)

Selectable (ON, OFF, safety position, loading of parameter set)

Integrated Digital Input1

2 inputs (use of analogue inputs1)

Digital Input Voltage

Urated = 24 V DC

Level "logical 1" (Digital Input)

14 V DC ≤ UH ≤ 28 V DC

Level "logical 0" (Digital Input)

0 V DC ≤ UL ≤ 8 V DC

Digital Input Current

ltyp = 18 mA (at 24 V DC)

Optional Digital Input

2 inputs

Optional Digital Voltage

Urated = 24 V DC

Optional Level "logical 1"

14 V DC ≤ UH ≤ 28 V DC

Optional Level "logical 0"

0 V DC ≤ UL ≤ 8 V DC

Optional Digital Input Current

ltyp = 2.5 mA (at 24 V DC)

Actual Value Position Feedback (Analogue Output)

4 - 20 mA

Number (Digital Output)

2 relay outputs

Digital Output Switching Voltage

= UV

Digital Output Switching Current

≤0.5 A

Function (Digital Outputs)

Selectable (position, set values, actual value)

Voltage + Input/Output Signals

3 x M12 plug, 5-pin (See connection kit)

Travel Sensor Connection

1 x M12 socket, 5-pin (For external potentiometer)


1 Analogue inputs can be used as digital inputs by external wiring with a resistor according to the operating instructions and software function.





Travel Sensor




Stroke (Linear design)

0-30 mm
0-50 mm
0-75 mm

Resistance R (Linear design)

3 / 5 / 5 kΩ

Min. Stroke (Linear design)

≤ 8 % of the travel length

Angle of Rotation (Quarter turn design)

0-93 º

Resistance R (Quarter turn design)

3 kΩ





Controller Information




Positioner Deviation

≥ 0.1% (adjustable)

Positioner PD Parameters

Adjustable

Positioner Initialisation

Adjustable or Manual

Type of Process Controller

Continuous Controller

Process Controller PID Parameters

Adjustable

Parameterization

at the device: menu selection context sensitive or help texts at the PC: Internet Browser MSIE

Text Display

2-line display with 16 digits each background light

LED

Profibus status (only with Profibus-DP option)

Buttons

4 fascia membrane protected buttons

PC Interface

RS 232 with PPP protocol for Internet Browser MSIE

Field Bus

Profibus DP V1
Profibus Interface - certified





Operating Conditions




Ambient Temperature

0 to +60 ºC

Storage Temperature

0 to +60 ºC

Control Medium

Quality classes to DIN ISO 8573-1

Dust Content

Class 3
(max. particle size 5 µm)
(max. particle density 5 mg/m3)

Pressure Dew Point

Class 4
(max. pressure dew point 3°C)

Oil Concentration

Class 5
(max. oil concentration 25 mg/m3)

Air Supply

1.5 to 7 bar

Air Consumption (when Idle)

0 lpm

Air Output

100 lpm
180 lpm

 





GEMU 1435 ePos Intelligent Positioner



Construction
The digital electro-pneumatic positioner detects the valve position with an external LongLife travel sensor. It has a solid housing with protected operating keys and an easy to read LCD display. The operating times can be set by integrated throttles. Connection and mounting to NAMUR is also possible.

Features

  • Simple and self-explanatory menu
  • Automatic initialisation function
  • Safety function during power or compressed air supply failure
  • Protection class IP 65
  • 3/4-wire type
  • Can be used with linear and quarter turn actuators
  • Operation with single and double acting actuators

Advantages

  • Separate mounting of positioner and travel sensor
  • Simple handling and commissioning
  • Simple electrical connection by detachable terminals
  • Automatic optimization of valve control during initialisation
  • No air consumption when idle



GEMU 1435 ePos Intelligent Positioner




Front View GEMU 1435 ePos

 









Specifications · Electrical Data · Operating Conditions · Main Functions · Materials · Travel Sensor · Additional Diagnostics from Version Index 01





Specifications




Type

1435

Field Bus

Without

Accessory

Accessory

Action

Double Acting
Single Acting

Explosion-proof Class

Without explosion-proof rating

Options1

4-20 mA actual value output
4-20 mA actual value output and heating element
4-20 mA actual value output Electrical connections M12 5-pin
4-20 mA actual value output, electrical connections M12 5-pin and heating element
Electrical connections M

Bình luận

HẾT HẠN

0963 922 287
Mã số : 8271596
Địa điểm : Hồ Chí Minh
Hình thức : Cần bán
Tình trạng : Hàng mới
Hết hạn : 23/08/2020
Loại tin :

Thường

Để mua hàng an toàn trên Rao vặt, quý khách vui lòng không thực hiện thanh toán trước cho người đăng tin!

Gợi ý cho bạn