http://auto-industryvn.com/dold-relay-il5881-0053805-1109090.html
• With reference to IEC/EN 61 557-8 (see also section "Notes")
• For DC voltage systems up to 12 ... 280 V
• Wide voltage range of measuring input UN DC 12 ... 280 V
(on request DC 24 ... 500 V with separate auxiliary supply,
Measuring range 20 ... 500 kΩ)
• Adjustable tripping value RAL of
5 ... 200 kΩ or 10 ... 500 kΩ
• Selective ground fault indication for L+ and L- allows fast fault finding
• Without auxiliary supply
• De-energized on trip
• 2 changeover contacts
• Automatic or manual reset, programmable
• With test and reset buttons
• Connection for external test and reset button possible
• Galvanic separated AC or DC auxiliary supply available as option
• Adjustable time delay as option
• 2 models available:
IL 5881: 61 mm deep with terminals near to the bottom to be
mounted in consumer units or industrial distribution
systems according to DIN 43 880
SL 5881: 98 mm deep with terminals near to the top to be
mounted in cabinets with mounting plate and cable
ducts
• DIN rail or screw mounting
• 35 mm width