Model FAPN202-R-5L
Type Conventional type
Power supply 220VAC 50/60Hz
Auxiliary power supply Ni-Cd battery (24VDC, 0.45Ah)
Circuit voltage 5, 24, 48 VDC, 24VDC
Alarm Verification time Thermal detector: 10 sec, Smoke detector: 60sec
Power consumption Monitoring: 25VA max. approx
Alarm: 40VA max, approx
Maximum number of devices supported Spot type smoke detectors: 30/zone (max.150/panel)
Alarm bells: 15 (24VDC, 10mA/bell)
Ambient temperature and humidity 0 to 40°C, 20 to 85% (RH)
Alarm input circuit loop resistance Less than 50Ω/Loop
End-of-Line resistor 10kΩ, 1/2W
Location lamps: 5 (30V, 2W/lamp) 15(24V, 24mA/LED), 21 (24V, 15mA/LED)
Materials (enclosure) ABS resin with 94UL-V2 flammability rating
Color Off-white (Nohmi White): Approximating Munsell N8.7 or equivalent
Weight Approx. 3kg