Model FRRU004-MOM4
Rated voltage range of SLC input power (S+,S-) 22.0 to 24.0V
Maximum SLC 24 VDC standby current (S+,S-) 250µA
Maximum SLC 24 VDC alarm current (S+,S-) 1mA
Rating for connected device power (Releasing device and NAC) 24VDC, 2A
Max. supervising current for external 24 VDC input power (24+,24-) 1.6mA
Wiring style NFPA Class B (Style Y)
End-of-line resistor value for notification appliance 5.1kΩ, 1/2W
End-of-line device for releasing device 5.1kΩ, 1/2W with diode
Maximum wiring resistance of output circuit wiring Refer to Wiring diagram
Maximum wiring capacitance of output circuit wiring 1µF
Operating temperature range 0°C to 49°C (32°F to 120°F)
Operating humidity range 0 to 93% (non-condensing)
Dimensions 106mm (4.17 inches) (H) × 106mm(4.17 inches) (W)× 29mm (1.14 inch) (D)
Applicable electrical box for installation North American 64mm (2-1/2 inches)deep 2-gang box
Standard 4 inches square box 38mm (1-1/2 inch)deep box